Description
Approvals/certifications | Certified to EN54-17/18 by the LPCB. |
Compatibility | Compatible with C-TEC’s XFP/ZFP CAST Addressable Fire Panels. |
Application/operation | Incorporates the functions of a switch monitor, zone monitor, simple switch interface and output unit in one device. |
Supply/operating voltage | 27 to 40V DC. |
Quiescent current | 1.3mA. |
Activation current | 5.5mA. |
Auxiliary relays | One volt-free single pole changeover relay rated at 1A @ 30 VDC (or 0.3A @ 125 VAC). Non-monitored. Clean contact. |
Auxiliary inputs | One monitored input that can be set to operate as: (1) a single zone monitor to support up to 20 ActiV detectors and 10 MCPs or (2) a monitored normally-open switch, triggered by a 470R. |
Indicators | Active (Lit Red): relay activated; monitored zone triggered or monitored switch closed; Polling (Flashing Red): communication check with the panel; Input Fault (Lit Yellow): fault detected on the monitored zone/switch. |
Connections | Six 45º screw-type connectors that can take 0.5-2.5mm2 cable: +Ve & -Ve Loop In; +Ve & -Ve Loop Out; Zone +Ve & -V. Also includes N/O, N/C & C relay connections. |
Product dimensions (mm) | 147 W x 87H x 22 D mm. Can be mounted on a standard 25mm UK flush or surface double gang back box. |
Construction & finish | ABS Polycarbonate plate with a 200 micron two-tone grey velvet polyester label with red and white detailing. |
IP Rating | IP40 when correctly installed. |
Weight | 122g. |
Operating conditions/temperature | -10ºC to +55ºC. |
Reviews